Sam's Laser FAQ, Copyright © 1994-2007, Samuel M. Goldwasser, All Rights Reserved.
I may be contacted via the
Sci.Electronics.Repair FAQ Email Links Page.

  • Back to Sam's Laser FAQ Table of Contents.

    HeNe Laser Testing, Adjustment, Repair

    Sub-Table of Contents



  • Back to Sam's Laser FAQ Table of Contents.
  • Back to HeNe Laser Testing, Adjustment, Repair Sub-Table of Contents.

    HeNe Problems and Testing

    How Can I Tell if My Tube is Good?

    A variety of faults can result in a HeNe tube not working properly. These can be the result of a large number of problems including a bad tube, a bad power supply, incorrect input voltage (or configuration), incompatibility between the tube and power supply, bad or incorrect ballast resistor, or defective wiring.

    If all you have is a HeNe tube but no power supply, see the section: Testing a HeNe Laser Tube Without a Compatible Power Supply for ways to determine if the tube is good. The following applies to both bare HeNe tubes and laser heads though some of the inspection and/or tests will require removing the tube from any enclosure.

    Several types of problems can prevent a HeNe tube from lasing properly or make it hard to start:

    It probably doesn't make sense to spend a lot of effort, time, or money to revive a 1 mW HeNe tube that can be replaced for $15. However, if you are ambitious or a new tube cannot be substituted easily (e.g., due to mounting restrictions), see the sections starting with: Repairing Leaky or Broken HeNe Tubes.

    Testing a HeNe Laser Tube Without a Compatible Power Supply

    First time laser enthusiasts are often confronted with this problem: Becoming the proud owner of a HeNe laser tube but no HeNe laser power supply and possibly no specs for the tube or assurance that it is even good. What to do? How can a quick inexpensive test be done to determine if the tube works?

    First, you need to determine the tube's power connections. See the section: Identifying Connections to Unmarked HeNe Tube or Laser Head if you aren't sure.

    There are many ways to power a HeNe tube for the purposes of seeing if it produces a beam. Almost anything that can provide enough voltage to get a few mA through the tube will result in at least a momentary flash of laser light out the end if the tube is good. There won't be any way of determining output power or whether the tube meets specs, but the knowledge that it lases at all may be enough to take the next step - the purchase or construction of a proper power supply.

    It is easy to use the family microwave to see if the tube is gas-intact if the tube will fit inside. See the section: Using a Microwave Oven to Evaluate and Revive HeNe Laser Tubes. While this won't tell you if the tube lases, if it fails this test, there is no need to go further.

    To test for lasing, current must be passed through the bore of the tube. A couple of options for a quick test power supply are:

    Even a high voltage AC supply with appropriate current limiting can be used safely for a few seconds only. (I've been sent HeNe laser tubes which have been operated on AC because the owner copied some power supply design off the Web and didn't know any better. The output power (what of it there was) gradually declined over a few minutes and then there was none.) And even with the rectifier voltage, the tube will be restarting once per cycle which is hard on it so don't run that for too long either. None of these are suitable to operate a HeNe tube continuously unless proper filtering and starting circuitry is added to turn it into a proper HeNe laser power supply.

    Don't go overboard though: Too high a voltage applied in the wrong place can arc straight though the glass at which point you have a rather boring high-tech sculpture. :( A very high current can also damage the tube very quickly, thus the need for the current limiting ballast resistance.

    With these power supplies driving the tube, if there is any output beam, even if it is weak or in the form of short flashes, the tube is probably good. However, there is no way to tell if it meets specs since HeNe laser output power is only maximum over a narrow range of tube current and these quick test power supplies are at most controlling only average current, not instantaneous current as would be the case with a real HeNe power supply. But, at least you know the tube isn't dead.

    Quick and Dirty Universal HeNe Laser Test Power Supply

    The following simple device can be used to confirm that a HeNe laser tube or head is not totally dead. It won't be able to help with output power or be safe to run for more than a few seconds but should produce some coherent output from any HeNe laser from 0.5 to 40 mW or more.

    It consists of the following components in series:

    Wire the output of the transformer in series with the rectifier(s) and ballast resistors. The positive output goes to the anode of the HeNe head or tube; the negative to the cathode. It doesn't matter whether the laser has an internal ballast resistor. Insulate everything VERY well. :)

    Powering the laser should result in flashes of coherent light, probably at the power line frequency (60 or 50 Hz). The amount of light will not be that impressive even with a perfectly good high power laser since the current is nowhere near optimal for any length of time, if ever. However, the presence of laser output would confirm that there is life.

    WARNING: Since centertap of transformer secondary should be grounded, both outputs of the power supply will be floating with respect to ground. Take care.

    HeNe Tube Lases but Color of Discharge Changes Along Length of Bore

    I've only seen this on a couple of HeNe tubes but the appearance is quite strange. At the anode-end of one, which I call the "Northern Lights" tube, the discharge color is perfectly normal - white-ish red-orange (salmon color), just as would be expected in any self respecting HeNe tube. However moving toward the cathode-end of the tube, the color changes to what appears to be a much more blue-ish white color (relative to the normal white-ish red-orange, though in absolute terms it may be more of a pink), typical of some sort of contamination. However, having a tube with the behavior provided a way (as you shall see below) of relating power output to the color of its discharge.

    In this condition, the tube still lased at a power level which relative to its rated output, is approximately proportional to how much of the bore has the correct color. In this sample, about 2 mW for a tube specified at 4 to 5 mW. I don't believe the starting or operating voltage has been affected very much.

    The explanation that makes the most sense is that due to the discharge current in the bore, the few N2 and O2 atoms (and any other party poopers that may have entered without an invitation) are being ionized and pushed toward the cathode of the tube leaving the desired helium and neon atoms to play at the anode-end. The contamination, whether due to a manufacturing problem or an air leak, is so marginal that nearly all of the unwanted atoms are swept from about half the length of the bore. However, the other HeNe tube I have like this had the color change in the exact opposite direct - correct at the cathode but blue-ish-pink at the anode, also reduced power. I now suspect that it may have been internal contamination. More research is needed. :)

    Another unusual characteristic of the Northern Lights tube was that the output power (what of it there is) peaked at a current somewhat higher than expected (8 mA as opposed to the 6 or 6.5 mA typical of this size tube). I don't know whether this is simply due to the overall contamination or that more of the nasty unwanted ions being swept from the bore when running at a higher current.

    This tube had an unfired getter which provided a means of cleaning up the contamination without a refill. A few weeks later, I got around to making the attempt. And the results are.... See the section: Repairing the Northern Lights Tube.

    Starting Problems and Hard-to-Start Tubes

    Some tubes seem to practically start on their own. Other won't perform even when you stand on your head, hold your breath, and provide the proper chants and sacrifices. :-) Note that this may not be a problem under your control. Apparently, even the Ph.D. physics types at major laser companies may not understand why apparently identical HeNe tubes from the same production run may vary in their ability to start by a large amount. See the section: About Hard Start HeNe Tubes. HeNe tube itself isn't to blame.

    However, it could also be that your power supply operating voltage, ballast resistor, and other factors may need modification. Of course, if the system used to work reliably and suddenly died, an actual power supply or wiring problem is most likely though a dead HeNe tube is also possible especially if the system has been unused for several years. But don't overlook the unlikely, but not impossible situation where your line voltage is low for some reason! Check it first. The discussion below is somewhat oriented to the situation where a HeNe tube or laser head is being assembled with a power supply (or parts have been replaced) and the combination just doesn't want to work properly. However, some of it also applies to actual failures as well. Where the power supply itself is suspect, see the section: Power Supply Measurements, Testing, Repair.

    There are several types of possible behavior depending on how well the power supply, ballast resistance, and HeNe tube are matched up, and if any of these as well as the wiring, are faulty. You first need to determine if the discharge is being initiated at all. If the starting voltage is adequate, there will be momentary flashes that may be extremely short and weak and only visible in a darkened room but operating current may not actually follow. Under marginal conditions, operating current will flow in response to the starting voltage but won't be maintained. These flashes will be brighter and longer in duration. The result may be a nice flashing laser. In fact, this progression is exactly what will be seen when operating a HeNe laser tube from a power supply on a Variac as the voltage is increased: Short flashes followed by longer flashes and at some point, a steady beam.

    WARNING: If your HeNe tube doesn't start after a reasonable length of time (like a minute), don't leave the power supply on overnight in a futile attempt to get it going. Starting is a stressful time for power supply components, especially some wide compliance designs, and an extended period with the very high starting voltage on parts of the circuitry may result in total failure. It could also result in electrical breakdown (arcing) inside the laser head or cable. If the laser is flashing, this may be ultimately bad for the tube as well. Turn it off, step back, and try to determine what is wrong.

    Where the power supply components and/or wiring is exposed and subject to dirt and grime, first, carefully clean everything to eliminate possible sources of electrical leakage, which can affect operation, particularly the very low current starting circuit. As an experiment, try warming up the unit (which drives off conductive moisture) with a hair dryer or heat gun on the 'low heat' setting. This may enable it to start more easily confirming the need for some housekeeping. :)

    First, vacuum and/or dust it off with a soft brush, then use mild detergent and water followed by isopropyl alcohol (rubbing or medicinal is fine as long as there are no additives). Give it ample time to dry completely. The hair dryer or heat gun can be used to help it along. You may now find that your starting problems have disappeared!

    If your tube or head has an external starting loop or tape (see the section: Power Requirements for HeNe Lasers), it must be cleaned thoroughly as well (or maybe it has become disconnected, is broken, or has shorted to the case!).

    There is also a possibility that something else is shorting out the power supply, possibly only when enough voltage is applied so it won't show up with an ohmmeter test. Sometimes, the ballast resistor inside cylindrical laser heads will arc to the case. This can be checked with an HV insulation tester or more easily for most people, by removing the end-cap(s) and visually inspecting (as well as smelling!) for evidence of arcing, or by disconnecting the anode wire and driving the tube directly from the power supply with an external ballast resistor.

    Assuming none of this helps, there are three types of behavior: (1) No action of any kind, (2) an occasional flash possibly at random intervals, and (3) a periodic flashing laser which never settles down to normal steady operation. However, the behaviors and their causes are not really always independent so read through all of the possibilities before replacing components or ripping your system apart!

    1. Tube does not fire at all. This means that the tube itself appears totally dead with no flashes inside and no evidence of a beam, even for an instant.

      This generally means that the starting voltage is inadequate for the tube or isn't reaching it, there are other circuit problems, or the tube is bad. In rare cases, shining a light into the tube will allow it to start. Tubes with longer and narrower bores (capillaries) will generally require greater starting voltage and your power supply may just not be up to the task. While tube manufacturers generally specify a starting voltage of 7 to 10 kV (or higher), typical tubes will fire with 3 to 5 times their operating voltage. Thus, a tube that runs on 1,700 VDC will probably start on 5,400 to 8,500 VDC.

      • There may be too much leakage in the anode circuit preventing the buildup of adequate starting voltage. The problem may be in the power supply itself or in the wiring to the HeNe tube. Corona discharge or arcing can result from inadequate insulation or component spacing as well as sharp points in the wiring or connections. Dirt and grime may also reduce the insulation resistance. A sizzling and/or ticking sound along with the aroma of ozone are indications of this sort of HV breakdown. Highly humid conditions may make the situation worse. For pulse (trigger) type starters, there may be too much capacitance as well.

        In the case of an enclosed laser head with a HV (e.g, Alden) connector, HV cable, and internal (potted) ballast resistor, there may be a breakdown in one of these components and it may only show up when starting voltage is applied (not with an ohmmeter).

        Allow the laser to attempt to start for 15 or 20 seconds and turn off the power supply. Immediately pull the Alden connector out of the power supply and discharge it on a metal surface. A nice long (e.g., 1/4") spark indicates that the starting voltage is probably adequate from the power supply and breakdown in the wiring is not likely. If there is little or no spark, either the starting voltage is low or zero, or there is a broken connection between the connector and the tube resulting in not much capacitance to store a charge.

        Here are two more tests for this situation:

        • Remove the negative connection from the ballast resistor assembly entirely - float it so the starting voltage cannot arc to anything. Connect the negative directly to the cathode of the HeNe tube or laser head case as appropriate.

        • Disconnect the anode of the HeNe tube and substitute your own ballast resistor and wiring.

        If the tube now starts, one of the original components was faulty (most likely the potted ballast resistor assembly if the negative connection runs through it) and this will need to be replaced.

      • There may be an open ballast resistor or break in the wiring inside an enclosed laser head. Check with an ohmmeter (with power off and the tube capacitance discharged!) all the way from the power supply or Alden connector to the tube terminals or mirror mounts (as appropriate). Don't forget to check the negative (return) connection and cathode ballast resistor (if present). Some laser heads have the wires simply clipped on or use little push-on connectors to attach to the tube mirror mounts, exhaust tip-off, or through-glass pins, and these have been known to pop off in shipping.

      • If you need to increase the input to start or obtain any sort of response but then must back it off substantially to reduce the tube current to the proper value, low starting voltage or one of the other related problems is indicated.

        Assuming the power supply and wiring check out and the tube is good, the only solution is to boost the starting voltage or use a different type of starting circuit (inverter instead of voltage multiplier, for example).

      • You may have an extremely hard-to-start tube. Whether this is just normal for your particular model tube or this particular sample, is due to it being old or unused for a long time, it is just tired with many hours under its belt, or some other problem, the result is that the specified starting voltage does not have any effect.

        Note that newly manufactured tubes requiring more than a second or so to start using a compatible power supply are usually rejected as defective and may end up in the hands of surplus dealers who may sell them as 'new' even though they don't meet specs. Thus, you may be more likely to end up with one of these hard starting tubes!

        • If a particular tube doesn't start right away because the tube itself is hard starting, cycle the power supply on and off a few times at about 1 second intervals. If it's going to start, it usually will by the third or forth try. I suppose the rapid rate of rise of the starting voltage does something useful. :) (How well this works will depend on the actual tube and power supply but most power supplies should survive the abuse.) While probably not a long term solution, if the tube starts, at least you know it isn't dead.

        • If the voltage doesn't discharge in a reasonable amount of time after powering down due to a lack of bleeder resistor, it may help to discharge the capacitance of the tube and power supply manually with a well insulated high value resistor (a few hundred k ohms to a few M ohms) before attempting to restart. Again, the rapid rate of rise of the starting voltage helps to ionize the gas. Where the tube starts reliably when this is done, it may be possible to add a high value (e.g., several hundred M ohm) resistor permanently across the power supply output.

        • For HeNe laser tubes with exposed bores like Spectra-Physics side-arm tubes, touching various glass parts of the tube (NOT the high voltage connections!) might also provide a capacitive path for the starting pulse. This applies more to pulse starters or those with s substantial component of high voltage AC, not the typical voltage multiplier with a DC output. Older Spectra-Physics exciters tend to have up to 50 percent of the starting voltage in the form of an AC waveform. Double check that the laser head case is grounded - a missing ground may result in starting problems. (More on this below.)

        • Shine a light on the bore in various places to see if that has any effect. On high mileage (probably) tubes, as with high mileage neon lamps or fluorescent lamp starters, a few photons can help ionize the gas. This isn't that common but is easy enough to check.

          And, it may not only be high mileage tubes. I recently discombobulated (translation: disassembled to harvest its organs) a vintage HeNe laser-based LaserDisc player and found a little incandescent lamp buried near the bore of the laser tube. It is even documented in the service manual (which includes the assembly procedure for the optical pickup), but there is no discussion as to its purpose. However, the only possible explanation is that the lamp was there to help a hard starting HeNe laser to start. It must have been included be able to use tubes that otherwise would fail to start quickly enough. I've seen this before with an HP-5501B that has a similar quirk - with the cover off, it starts easily. But with the cover on, it may take a minute or more to start. But for a manufacturer to deliberately add a light bulb to aid starting in a production unit is so strange. Well, I did have a professor whose motto was "If it works, use it". :)

        • Another test is to try the tube with reverse polarity on its input. Connect the positive output of the power supply to the ballast resistor (don't omit this!) and then to the cathode (can electrode) end of the HeNe tube. Connect the negative of the power supply to the anode of the tube. You are only doing this for testing! Do not be tempted to leave the tube wired this way permanently should it actually start.

          Based on tubes I have tested, the starting voltage is much lower with the anode and cathode connections interchanged. However, the voltage drop across the tube when running with reverse polarity is much higher than with correct polarity. Thus, the tube may not run within the normal operating voltage range of your power supply even if the discharge is initiated - more likely it will just pulse.

          Nonetheless, even if it just pulses, at least you know the tube is not totally dead. If the tube is otherwise undamaged, there should also be an indication of (at least weak) laser output from the business end of the tube. Perhaps, all you need is a power supply with higher starting and/or operating voltage. An inverter type starter using a flyback transformer appears to be particularly good for hard-to-start tubes. Unfortunately, I do not know of any reliable way of determining the likelihood of success without actually trying it.

          I have one 5 mW HeNe tube that requires (depending on its mood) as much as 15 to 20 kV to start (it should be less than about 10 kV). However, once started, it runs with a normal operating voltage of about 1,800 VDC.

          WARNING: Do not let the HeNe tube run for any length of time with reverse polarity as damage may occur due to heating and sputtering at the anode end of the tube.

        • Carefully heating the tube (with a hair dryer, NOT a propane torch!) may help to get it started in some cases. I've only heard of one instance of this and have not tried it myself but it should be easy to experiment. A tube that responds to this treatment is probably one what just has trouble starting the first time after being off for awhile but restarts easily when warm. However, what may really be going on is that you are heating the power supply circuit board nearby reducing leakage in the anode circuit (see above) or bringing a ground in close proximity to the tube (see below).

    2. Tube flashes occasionally for the very briefest of instant, possibly at random intervals. There may or may not be a laser beam accompanying the flashes. Depending on the situation, it may just appear to give up and revert to (1), above. This may be a protective feature of certain power supplies or an indication that the starting pulse is being diverted by an electrical leakage path, corona, or arcing somewhere.

      This sort of behavior is probably more likely with a pulse type starter but can occur with other types as well. What is likely happening is that the energy is insufficient to fully ionize the gas inside the bore of the HeNe tube so the discharge doesn't 'catch'.

      In addition to the other possibilities listed above and below:

      • Check for missing grounds. Where a pulse starter is used or a marginally compatible power supply where the high rate of rise of the starting voltage is needed to start it is possible that like many fluorescent lamp fixtures, a grounded metal plate is needed near or in contact with the tube to provide a capacitive path to aid initial ionization of the gas. Operating the laser (or fixture) on an ungrounded outlet, not installing a foil shield or not properly grounding it, or replacing the HeNe tube with one that doesn't have such a 'feature', might result in erratic starting - perhaps no action at all or maybe an occasional flash but not actually remaining on or taking a long and random time to 'catch'. If putting your hand on the tube (carefully avoiding the high voltage terminals!) results in consistent starting, lack of proper grounding would be confirmed. (This applies to uncooperative fluorescent fixtures as well.) Add a wrap of aluminum or copper foil and attach it to earth ground. I have only heard of one case that might have been due to a missing ground so I suspect this is quite an unlikely scenario!

      • Make sure the anode leads are as short as possible to minimize stray capacitance.

    3. Tube flashes momentarily - longer than an instant possibly up to a second or two - but does not 'catch'. During the time the discharge is on, there is a laser beam.

      What happens is that the discharge is initiated but the voltage drops too much at the tube anode and the discharge goes out. This cycle repeats resulting in a flashing HeNe laser.

      To produce a stable discharge, the following must be satisfied:

      • The sum of the effective resistance of the power supply and the ballast resistor and the (incremental) negative resistance of the tube (dV/dI at the operating point) must be greater than 0.

      • The voltage across the tube must be above the minimum for the tube at the operating current.

      • The current must be above the minimum for the tube/power supply/ballast resistor combination.

      These factors are not independent. Since the negative resistance and sustaining voltage of the tube are not normally specified and depend on current, some amount of trial and error may be required to achieve consistent stable operation but in most cases it really is very easy.

      Cycling behavior can be due to several factors:

      • Poor power supply voltage regulation or excessive ripple. Until the tube fires, there is essentially no load on the supply resulting in much greater voltage than under load. Except for a high compliance type of design where this is needed to produce the starting voltage, minimizing this difference will improve stability and reduce the voltage needed for stable operation.

        If the transformer or inverter drops too much under load, the tube voltage may fall below the minimum for the tube/ballast combination as soon as it starts. This cycle will repeat continuously or it occasionally may catch.

        Use a higher voltage and larger ballast resistor, and/or increase the uF value of the main filter capacitor (and/or the one in the DC supply to an inverter type supply as well if it isn't regulated).

        Minimum capacitor values for less than 5 percent voltage ripple (typical voltage and current requirements):

        • Line operated supplies: .5 to 1 uF (2000 V, 5 mA).
        • Inverter output: .005 to .01 uF (10 kHz, 1,800 V, 4 mA).
        • Unregulated inverter input: 15,000 to 20,000 uF (12 V, 1 A).

        Actual ripple in the current to the tube may be several times greater than this since it depends on the change in voltage with respect to the total effective resistance of the PS+tube+ballast resistor combination). However, the resulting ripple in the optical output power will be 2 to 10 times lower than the ripple in the current depending on operating point. The lowest will occur around the tube's optimal current specification.

      • Ballast resistor too large for the operating voltage. The operating current falls too low resulting in increased (magnitude of) negative resistance. Once the total system resistance goes negative, the discharge becomes unstable and goes out. The result is a flashing laser like a neon bulb relaxation oscillator.

        For an unregulated power supply, increase the operating voltage and/or decrease the ballast resistance.

        For a regulated power supply, decrease the ballast resistance so that the voltage for the desired operating current falls within its compliance range.

      • Too much stray capacitance and/or inductance in anode circuit. The system is behaving like a relaxation oscillator as the capacitance charges and then discharges through the tube. The wiring inductance causes the current from the main supply to lag too far behind the starting current and the discharge goes out.

        Shorten the wiring - minimize the distance between the power supply and ballast resistor, the ballast resistor, and tube anode, and don't use long runs of high voltage coax (which may have higher capacitance). Increasing the energy of the starting circuit slightly may help as well.

      • For laser heads in particular, the additional capacitance resulting from the metal case may increase the minimum stable tube current by up to 1 mA or more - and thus require changes in the power supply and/or ballast resistor. So, if you tested the HeNe tube and power supply on your workbench but the enclosed system is unstable, this may be the reason.

      • Power supply polarity is reversed. The voltage drop across a HeNe tube operated with the cathode and anode interchanged is higher than under normal conditions. However, required starting voltage is much lower. The result is likely to be a pulsing laser. Double check your wiring and terminal connections. I have also seen commercial power supplies mislabeled! See the section Making Measurements on HeNe Laser Power supplies if you need to actually test for reverse polarity.

    Also see the sections: How Can I Tell if My Tube is Good?, About Hard Start HeNe Tubes, Testing a HeNe Laser Power Supply, Power Supply Construction Considerations, and Adding a Start Wire.

    About Hard Start HeNe Tubes

    As noted elsewhere, apparently identical HeNe tubes made on the same production line may differ widely in their starting performance. While one sample may start absolutely instantly, another one that is indistinguishable may take several minutes to wink on. A newly manufactured HeNe tube that requires more than a second or so to start using a compatible power supply is generally rejected as defective. Guess who may end up with these - surplus dealers, and ultimately, you! The condition may get worse with use so some high mileage tubes could indeed be a lot worse in this department - possibly to the point of being virtually impossible to start even if they were within spec when new.

    As far as I can determine, the fundamental physics behind this phenomenon may not even be well understood by the major laser companies. The only meaningful data is statistical, because even a give tube with a given power supply will have dramatically different start times from attempt to attempt, as will tubes built side-by-side through the entire production process.

    Tubes that are kept in dark cold environments for long periods of time don't tend to start well. But, once one of these tubes is started successfully, restarts will likely be instantaneous, or at least reasonably quick. However, left overnight, they will revert to being uncooperative.

    Also lower fill pressures and cleaner tubes make for hard starting - not to mention power supply variables.

    Some manufacturers (e.g., Melles Griot) use a conductive 'start-tape' running the length of the tube attached to the anode electrode to aid in starting. It's not even really proven that this improves performance (and I've found that it can be a source of electrical breakdown problems. I've never noticed any difference in the speed of starting after removing the start-tape). Uniphase had a pointed electrode inside the anode mirror sleeve to aid in starting but it isn't obvious that it made any statistical difference either. There has even been talk of using a trace of radioactive gas (as used to be common in neon indicator lamps and glow tube fluorescent starters), but this of course would probably not be a popular idea today!

    A given production line may still have hard-start related yield problems from time to time (which kind of suggests the Ph.D physicists don't understand it). Funny thing is, no one can tell anything that's different on a hard-starter versus a regular one.

    Adding a Start Wire

    As noted elsewhere, many HeNe laser heads have some type of starting wire or start tape running from the anode along the tube to the vicinity of the cathode. In most cases, this actually has little or no effect on starting, and may end up becoming a problem where electrical leakage can cause starting problems. The reason it doesn't usually help is that with the common coaxial tube construction with a full length gas reservoir, the electric field produced by the high dV/dt of the initial starting voltage rise can't be anywhere near the bore, where it's needed. This is particularly bad with Melles Griot and Aerotech tube construction since the discharge path is not near the glass surface anywhere. On Hughes and NEC tubes, there is a location near the cathode where the center of the tube is exposed.

    For some hard start tubes that otherwise run well without current drop out problems, adding a start wire directly from the anode with a few turns wrapped around the tube near the cathode may help starting dramatically. For example, on Spectra-Physics side-arm laser tubes, there is a section next to where the cathode attaches to the main bore where adding a start wire may work quite well. This allowed an SP-155 which would almost never start at normal line voltage to start instantly first time every time.

    Use a well insulated wire connected before the final ballast resistor. Wrap the end a few times around the narrowest section of the tube near the cathode or use a metal clip. Some experimentation may be required. Just try not to zap yourself excessively during testing. :)

    However, if used with a some linear power supplies having a voltage multiplier starter (probably without a final diode/filter stage), the tube must run stably substantially above its lower current dropout point or else the start wire will tend to turn the tube off as well as turn it on and the result will be a flashing laser, which is usually not a good thing. Adding a HV diode in series with the start wire might help, but I haven't tried it.

    Possible Causes of No Output with a Normal Discharge Glow

    Where the HeNe tube starts - there is a stable glow discharge and it is the correct color (bright white-ish red-orange, see the section: How Can I Tell if My Tube is Good?), there are a few possibilities that are not due to a bad HeNe tube or laser head:

    And, for other-color HeNe tubes which have much lower gain for a given length than red HeNes, all of the above may apply. The following comments were prompted by questions about a non-lasing short green HeNe tube (similar to a Melles Griot 05-LGR-024, 215 mm in length:

    (From: Lynn Strickland (stricks760@earthlink.net).)

    Those things are touchy, touchy, little SOBs. They usually have an almost flat HR and OC combination. If it does lase, it will probably be a few tenths of a mW at best. Probably have to walk the beam AND tweak both ends for any hope. Try some magnets too, for 3.39 micron suppression. In general, low power greens are a bitch to tweak.

    Note that the green discharge is more 'pink' (red tubes more 'orange'). Fill mixture is a little different, but the different color mostly due to lower fill pressure - which is why greens have shorter lifetimes than red.

    Possible Causes of Low Output with a Normal Discharge Glow

    Where the discharge color is normal and the tube current is known to be reasonably correct but the output is weak, there can be a variety of causes. (Of course, most of this also applies to no output but this is covered in the section: HeNe Tube Problems and Testing.) The following applies when the output power just isn't as great as expected:

    Doughnut Mode Beam from TEM00 HeNe Laser

    Occasionally, a HeNe (or other) laser designated as TEM00 will actually output a beam which looks like a doughnut or torus - with a hole in the middle. It's running with a not quite TEM00 mode structure - a doughnut mode. Since this should be a TEM00 laser with a single transverse mode Gaussian beam profile, that's normally considered a bug. If it's outputting decent power (compared to its specifications), the cause isn't likely to be dirt inside the tube or imperfect mirror alignment.

    More likely, the manufacturer accidentally used too large a bore for the length of the resonator and the mirror curvature. For example, if this is a green (543.5 nm) HeNe laser, they may have used a bore sized for a red (632.8 nm) HeNe laser by mistake resulting in a mode diameter that is too large. Or, it might have been designed on the hairy edge, size-wise, in an attempt to get as much power as possible out of the tube and the engineers weren't lucky that day. With a correctly sized bore, slightly incorrect mirror alignment would result in lower power but maintain a TEM00 beam profile.

    If you had been the original owner, the laser might have been replaced under warranty. As it is, you now have what I generally call an "interesting" laser. :) Or, since the specifications are often only with respect to "95% mode purity", if the hole represents less than 5 percent of the power, maybe it's considered acceptable, though I can't imagine anyone being entirely happy with a laser that's supposed to be TEM00 having a hole in the middle of the beam unless all they care about is the number of photons per second!

    However, even with too wide a bore, it may be possible to adjust the mirror alignment to obtain a TEM00 beam. Gain access to the cathode-end mirror mount (to avoid a shocking experience) and allow the laser to warm up completely in the orientation that will be used. Aim the laser at a screen of some sort like a white business card, and gently press sideways on the mirror mount from orientations every 45 degrees or so (top, bottom, left, right, and the diagonals). Closely examine the spot shape to see if it pops into TEM00 at any time while still maintaining near-maximum power. If it does, it should be possible to adjust the alignment as described in the sections starting with: Problems with Mirror Alignment. A power meter will be useful to assure that the output power is still near maximum. It may in fact end up being maximum with the TEM00 beam, though some other beam profile when cold. Very likely, the alignment will be very critical. Several attempts with multiple warmup cycles (to allow the metal mirror mount stems to settle in) may be needed to achieve consistent behavior. I adjusted a green HeNe laser head that formerly had a doughnut beam. It now starts out TEM01 but becomes a beautiful TEM00 once it warms up, and significantly exceeds spec'd power. But I haven't decided whether a consistently interesting doughnut beam or a boring high quality TEM00 beam only when warmed up is preferable. :) CAUTION: You could make the laser worse or dead by attempting mirror alignment. So unless you've done this successfully before, it may be best to leave well enough alone and enjoy the unusual behavior. There's nothing else you can do about it!

    Unstable or Flickering HeNe Tube

    Where your HeNe tube starts and lases normally but is unstable, flickering or going out and then restarting whenever the power line voltage dips slightly or for no apparent reason, the problem may be power supply or HeNe tube related. It is also not unusual for this to start happening after the system has been on for awhile due to characteristics of one or more of the components changing slightly.

    A different power supply or slight adjustments or modifications may make your HeNe tube happy, at least temporarily. However, where the HeNe tube is an inexpensive vanilla flavored variety, replacement may be the easiest solution if it turns out to be marginal. :-)

    Sputtering or Erratic HeNe Tube

    This behavior is somewhat similar to the some of the compatibility problems described above. However, it could be much more random and may only occur during warmup.

    The symptoms are that the tube may start normally but then go off and restart, possibly quickly and unpredictably. One possible cause is a bad internal connection between the cathode can and its attachment to the mirror mount where the negative lead of the power supply is hooked up. The type of construction susceptible to this malady is where a 'nipple' on the end of the aluminum cathode can is swaged (pressed/squished) into the mirror mount rather than actually being attached by spot welding or via a spring contact. After many thermal cycles, the swage can loosen resulting in intermittent contact especially as the tube heats and parts expand. (This is sort of the same problem that aluminum house wiring can have if improper termination techniques or devices are used, but in that case, the consequences can be much more disastrous!) Any sort of high resistance increases the required tube voltage since the mirror mount has a higher 'cathode fall' voltage drop. The discharge will likely go out and the power supply will then attempt to restart. In some cases, the discharge may strike to the mirror mount itself (look for a glow near the mirror) and if this persists, will eventually destroy the mirror. (See the section: Damage to Mirror Coatings of Internal Mirror Laser Tubes) After the tube warms up sufficiently, since aluminum expands faster than steel or Kovar, the problem may disappear once the connection tightens. However, until then, the intermittent contact and many restarts is hard on the power supply and nearby mirror.

    Assuming the power supply and tube are properly matched and the power supply isn't defective, this is a defective HeNe tube. No cure is possible. This is a relatively unusual problem (I've only seen it in two (2) HeNe laser tubes so far) so first check external connections and make sure your HeNe tube and power supply are properly matched. If its maximum voltage is marginal, as the tube heats up, the voltage drop may increase just enough to result in erratic behavior. However, one possible difference between this and a bad cathode connection is that with the latter, the condition may clear up once the tube heats up since the expansion of the aluminum cathode will improve contact. The marginal voltage situation will just get worse. The power supply itself could also be defective. The easiest way to determine which is at fault is to swap the PSU and/or tube with known good units.

    I've seen this malady on a few older Melles Griot HeNe lasers. On newer ones, a thin metal conductor has been added - presumably in response to this type of failure - connecting the spider/bore support (which is in good contact with the cathode can) directly to the end-cap. It is spot welded at both ends.

    Also see the section: Unstable or Flickering HeNe Tube.

    Alden Connector Problems and Repair

    While Alden connectors rarely give problems, a loose or corroded contact inside the plastic shell can result in all sorts of intermittent behavior including hard starting and repeated restarts or flickering. Though rare, arcing is also possible from a damaged cable, generally where a HV coax enters the Alden shell. Any heating of the Alden connector - even if NOT accompanied by 6 foot flames - is an indication of trouble with the contacts as there should be absolutely no detectable power dissipation in the connector! :) So, before you blame the laser head or power supply, make sure the Alden connections are secure.

    The male pins can be cleaned with a file or fine sandpaper. The female contacts can be tightened by wedging a small flat-blade screwdriver inside the connector between the side and the plastic contact support. Entire replacement Alden connectors are readily available or can be salvaged from dead laser heads or power supplies. To avoid the possibility of arcing or a shocking experience, use at least 2 layers of heat-shrink tubing for insulation with a minimum of 3/4" beyond the bare wire sections, and stagger the splices. Add another layer of heat-shrink over the completed splices.

    Cyclical Variations in Output Beam Power

    A HeNe laser that is in good condition will produce an output beam that is quite stable and will have no visible (at least by eye) variations in output power though a laser power meter will show fluctuations over various time scales of a few percent even after warmup unless it is high performance amplitude stabilized laser. A typical laser tube will have a "mode sweep" specification of between 2 and 20 percent depending on type and size (smaller tubes typically have poorer performance). As the tube warms up, this cycling will start out slowly, speed up and peak, and then taper off as the system stabilizes thermally.

    Note that if the discharge is actually going on and off, the cause is entirely different - an incompatibility with the power supply, incorrect ballast resistor, low line voltage, etc. See the section: Unstable or Flickering HeNe Tube.

    However, sometimes you will find a laser that exhibits significant periodic variations in output intensity even where the discharge is perfectly stable. There are two types of phenomena depending on the period of the power cycles:

    Reasons for Short HeNe Tube Lifetime

    As noted, sealed HeNe should last many thousands of hours with no noticeable degradation in performance.

    If you are experiencing excessively short life (e.g., a month instead of years), the first things to check are operating current and polarity. See the section: Making Measurements on HeNe Laser Power Supplies. Of course, if you omitted the ballast resistor, life will likely be very short. :-(

    If the HeNe tube and power supply are mismatched, one can damage the other. For example, running a 1 mW HeNe tube on a power supply designed for a 35 mW HeNe tube may not only result in too high a current by design (e.g., 8 mA instead of 3 mA) but may also result in much higher current if the compliance range of the power supply is exceeded (i.e., the voltage across the HeNe tube is much lower than the power supply can handle). Conversely, attempting to power a 5 mW HeNe tube using the power supply from a barcode scanner (designed for a .5 to 1 mW HeNe tube) will likely result in a blown power supply. Just because the high voltage connectors mate and/or the tube lights up doesn't imply anything about compatibility! Also note that maximum optical output occurs at the optimum operating current - too high or too low and it goes down. (Operating current for yellow, orange, and green HeNe tubes is even more critical than for the common red variety so setting these up with an adjustable power supply or adjusting the ballast resistance for maximum output is recommended.)

    New and even used HeNe tubes and power supplies from reputable surplus dealers will generally last a long time if not abused. But, much of what you get at swap meets and hamfests has been pulled from equipment for one reason or another. So, the problems you are experiencing may have nothing to do with your setup!

    (From: Lynn Strickland (stricks760@earthlink.net).)

    Speaking as a non-physicist....

    There are so many variables in a gas discharge, it's a game of averages. That's why the power supply business can be so tricky - and why, for the power supplies you can look inside of, you see so many modifications. That, and the rate at which electronic components go obsolete keeps it in a continuous state of flux (no pun intended).

    Reasons for the variability in lifetime and failure mechanisms from design to design revolve around design fill pressure and gas mix, operating current, distance from capillary bore-end to cathode, optical design (some designs are more sensitive to misalignment than others). Also power supply variability, ballast resistor value differences, operating current tolerances (often set at, say, +/-0.2 mA).

    Gas lasers can be a pain, but for a lot of applications, they're still the most cost effective solution -- in some cases the only solution.

    Power Variations Due to Lack of Mirror Substrate Wedge

    The only surfaces of a HeNe laser cavity that should be aligned are those of the two mirrors. Any others that are perpendicular to the optic axis will cause reflections that can affect the power and stability of the laser by forming a Fabry-Perot etalon - a secondary resonant cavity. (Note that the following discussion does *not* deal with the stability aspects of reflections - which is a very complex subject unto itself - but only with how they affect the waste beam and main beam output power.) Perhaps surprisingly, the outer surfaces of the mirror glass or substrate are a possible source of reflections that can cause peculiarities, if not actual problems, in the laser's power stability. Both the HR and OC mirrors can be at fault and affect the power from the main beam out the front of the laser as well as the waste beam out the back. But it is power variations of the waste beam that are usually most dramatic, except for some cases of goofups in manufacture, mostly of "other color" lasers..